| Topic: Stairways – Strength | Issued by: Chief Compliance Officer |
| Statute: General Regulation 91-191 | Date Issued: January 9, 2026 |
| Section: 115(1)(a) | Date Revised: |
Question
What are the strength requirements when building stairways?
Answer
As per paragraph 115(1)(a) of the General Regulation 91-191, stairways must be able to sustain a live load of 4.8 kPa. However, the National Building Code of Canada – 2020 (NBC) has two sets of design specifications for strength and rigidity under uniform loading:
To align with NBC requirements, employers can design stairs that meet a specified load of 1.9 kPa, provided the stairs are intended for its corresponding application, as listed above.
Many conditions must be satisfied to ensure stairways are NBC-compliant. See illustrations below that visually demonstrate the specific NBC criteria for wooden stairs.


Supported – The stringer must be structurally supported at both the top and bottom. The bottom of the stringer must sit on, and be fastened to, a floor, landing, or slab. At the top it should either sit on a ribbon board attached to the floor system or landing. Alternatively, a suitable engineered hanger would be acceptable.
Secured – The stringer must resist rotation (especially important for open riser stairs). Blocking between stringers may be used to prevent movement.



Definition of words from the NBC:

All measurements are nominal sizes.
Stair treads of lumber, plywood or OSB
Stair treads of plywood or OSB, not continuously supported by the riser:
115(1)(a) An employer shall ensure that a stairway is of sufficient strength to sustain a live load of 4.8 kPa.